P a g 2 � 2 <br />C1010-019 (126 W Beech St) <br />November 8, 2010 <br />9. Provide insulation bafFle at each truss per Section 502.1.4.5 Washington State <br />Energy Code (WSEC). Show requirement on plans (do not simply reference code <br />section). <br />10. Provide attic ventilation calculation. Show size and location of required ventilation. <br />11. Provide details for guard construction; show posts and in-fill members per R312 and <br />Table R301.5 IRC. <br />12. Provide deck lateral load connection per R502.2.2.3 and Figure 502.2.2.3 (deck <br />attachment for lateral loads). Show on plans. <br />13. Specify post/footing and post/beam connections at new deck capable of resisting <br />uplift and lateral displacement. <br />14. Provide site address per R319.1 IRC. Maintain visible address from the street during <br />construction. Provide note on drawings. <br />Please prepare a response letter showing where each item in this correction letter is <br />addressed on the plan set. <br />Upon resubmittal of the drawings, your application will be given priority and plan review will <br />recommence. <br />All required submittals shall be of sufficient detail and contain sufficient information to ensure <br />that the proposed structure will be constructed in compliance with all adopted codes. <br />Sincerely, <br />� <br />� � �� �� <br />� <br />Jeff Heilman <br />Development Technician <br />425-257-8976 <br />Email: iheilman@ci.everett.wa.us <br />S/kcullison/heilman/C101O-019 Q26 W Beech SQ <br />