Laserfiche WebLink
Providence Hospice and Home Cdf�fSnohomish Co <br />Chapter 246-335 WAC Hospice Care <br />New 16 Bed Hospice Center <br />Building Code Issues IBC, IFC, and NFPA 101 <br />T2 Heat-producing equipment (range) is not allowed to be in or open to a corridor in the 2000 <br />NPPA 101. Review the CMS Categorical Waivers on the use of heat-producing equipment. <br />This waver is only for nursing homes. Therefore, it most likely would not be allowed in a <br />hospice center. <br />Also, consider the impact, soine of which inaybe adverse, having and open "cooking" area on the <br />rest of the population. Some odors may cause an unfavorable out come on another. <br />http://www.cins.gov/site-search/search-res��lts.html?q=Cate�orical%20Waivers <br />http://www.cins.Qov/Medicare/Provider-Enrollment-and- <br />Certification/Sw�veyCe�rti�icationGenInfo/Downloads/SCLetterl2 21-.pdf <br />2000 NFPA 101: 18.3.6.1 and NFPA 101: 3.3.13.2 <br />T3 Resident/patient room doors that open to the corridor do not need to have a closer. <br />NFPA 101: 18.3.6.3 and IBC 407.3.1 <br />T4 It may be permissible to have a dining room that is open to the corridar. Review the cited <br />section. <br />NFPA 101: 18.3.6 <br />TS During construction indicate what method and means will be employed to keep the fire-alarm <br />and fire-sprinkler system operational. <br />IFC 901.7 <br />T6 Provide at least 2 smoke compartments for each building with sleeping units. <br />IBC 407.5 <br />T7 Review the requirements for Carbon Monoxide alarms. <br />IBC 908.7 <br />T8 A type 1 hood is not required for your range. <br />IMC 507.2.1 <br />T9 Review the requirements for "suites" in an I-2. <br />IBC 407.4.3 and NFPA 101: 18.2.5 <br />T10 If this area is designed as a"suite" the area must be separated from other areas by using a smoke <br />partition. <br />IBC 407.4.3.2 and NFPA 101:18.2.5.4 and 18.3.6.2 <br />T11 If the patient care area is designed as a"suite" the wall common to the patient room and the hall <br />only needs to meet the requirement of a non-rated partition. <br />IBC 407.4.3 and NPPA 101:18.2.5.4 <br />Page 5 of 10 Plan Review Comments for Project # 60542870 ���� <br />_ � <br />