Laserfiche WebLink
Providence Hospice and Home Ca�� :;� Snohomish Co <br />Chapter 246-335 WAC Hospice Care <br />New 16 Bed Hospice Center <br />T12 It is permissible, if the sleeping area meet the requirements of a suite as listed above, to have <br />sliding "barn" doors on the patient rooms. Doors in a"partition" wall do not have listed <br />requirements. <br />IBC 407.4.3 and NFPA 101: 18.2.5.4 <br />T13 It is permissible to not have a continuous grab bar at the rear of an accessible toilet. <br />ANSI Al 17.1: 604.5.2 (see the exceptions) <br />T 14 Lnsure that the door to the laundry chute meets all current requirements. <br />IBC 713.13.1 and 713.2 and table 716.5 <br />WAC 246-335 Issues <br />T15 Pr<�vidc thc fc�llc��vin�, al thc s��mc timc ���hcn submittinb to tl�e city: <br />1) Two sets of architectural drawings prepared, stamped, signed by a licensed architect. <br />2) Two copies of a life safety plan. These drawings need to show delineate all life safety <br />aspects such as but not limited to where rated walls, rated doors, egress lighting, exit light <br />and exit locks and latches are located. <br />3) Two copies of a floor plan showing all the furniture, waste cans <br />4) Two sets of inechanical drawings prepared, stamped and signed by a li:censed <br />professional. <br />5) Two sets of electrical drawings prepared, stamped and signed by a lice-nsed professional. <br />6) Two sets of inechanical drawings prepared, stamped and signed by a licensed <br />professional. <br />7) Provide one copy of the functional program. <br />8) Provide one written copy of the facilities emergency disaster plan <br />WAC 246-335-195 (1)(b) <br />T16 Provide a functional program that fully deliueates the relationship to ihe hospi�tal. I�lcludiug but <br />not liinited to the following: <br />1) Laundry <br />2) Reception <br />3) Janitorial <br />4) Food service <br />5) Emergency Preparedness. <br />6) Emergency power. <br />7) Pharmacy <br />8) Laboratory Services <br />9) Building Maintenance/repair <br />WAC 246-335-195 (1)(a) <br />Page 6 of 10 Plan Rcview Co�nments fc�r Project # 60542870 �, ���� <br />