Laserfiche WebLink
• <br />5. If heating and air conditioning system utilizes an exterior unit, show its location on the <br />site plan. <br />6. Below grade walls are required to be insulated to minimum R-21 on the interior which is <br />6 inches thick. A 2 x 4 wall with a one inch air space does not provide sufficient depth <br />for R-21 insulation. Correct cross section ��X" on sheet 4. Show ali components of <br />furring including pressure treated members that are in contact with the concrete. <br />7. Specify required fire blocking per section R302.11 IRC on wall sections. Do not simply <br />reference the code section. <br />Please prepare a response letter showing where each item in this <br />cor�-ection f�tte� is ae➢dressed on the pla� se�. <br />Upon resubmittal of the drawings, your application will be given priority and plan review will <br />recommence. <br />All required submittals shall be of sufficient detail and contain sufficient information to ensure <br />that the proposed structure will be constructed in compliance with all adopted codes. <br />Sincerely, <br />�'� <br />�, =��,�.�,� - _ � <br />Y <br />Jeff Heilman <br />Development Technician <br />425.257.8810 <br />Email: jheilman@everettwa.gov <br />S:A1Cominon\Clerlc�l\7HeilrnanACI510-03�> (2ll3 HoytAve).dric <br />