Laserfiche WebLink
• • <br /> Occupancy Comments: <br /> 1. The building occupancy and occupancy load should be shown on the <br /> drawings, per IBC section 2606.7. <br /> Sheet G1.0 — Building occupancy and occupant load added. <br /> Egress Comments: <br /> 1. Floor plans should be submitted indicating the location of the replacement <br /> overhead skylights relative to egress elements, per IBC section 2606.7. <br /> Sheet G1.0 — Construction type (III-A Sprinklered) added. Per IBC section <br /> 2606.7, light diffusing systems are allowed in buildings equipped with an <br /> automatic fire sprinkler system. <br /> Construction Comments: <br /> 1. Building sections should be submitted to indicate the height of overhead <br /> skylights relative to grade level, and the building construction type should be <br /> shown on the drawings per IBC section 2608.2 (3). <br /> Per IBC section 2608.2.3 Exception 1, height limits do not apply to <br /> buildings equipped with an automatic fire sprinkler system. <br /> 2. The drawings should indicate if the building is sprinklered with an automatic <br /> fire detection system and the construction type, per IBC section 2609.1. <br /> Sheet G1.0 — Construction type (III-A Sprinklered) added. <br /> 3. The roofing details should indicate if the '/2 inch cover board is new, the base <br /> ply is new, and the other materials referenced in the detail are existing or <br /> new. <br /> Sheet A3.1 — Details have been modified to show all new materials as <br /> 'NEW' and all existing materials as `EXISTING'. <br /> 4. The drawings should indicate the existing roofing materials and if any of the <br /> current roofing is being removed prior to the new roof installation. <br /> Sheet A3.1 — All details have been modified to show a dashed line <br /> representing the layer of single-ply roofing to be removed. <br /> a3 <br />