Laserfiche WebLink
Plan Check No. B-39172 <br />Marach 9, 1993 <br />Page Two of Two <br />ITEM 17 <br />No safety glazing is indicated, please indicate on the elevations. <br />ITEM 21 <br />Typical exterior guardrail section on Sheet A2 incorrectly states required minimum spacing. <br />ITEMS 23. 24 & 2� <br />A stair section and exit balcony section are required to indicate the construction of these azeas, <br />handrails, guardrails, etc. <br />Please also p;ovide justifying test data for construction assemblies. <br />ITF.M 30 <br />The 60" diameter tuming circle must be located within the kitchen, not adjacent to the kitchen. <br />ITEM 36 <br />Please provide bathroom, laundry room and range exhaust fan sizes. <br />Please indicate outdoor air inlet locations on the pllns. <br />Due to this requirement for additional plan review, all further time spent reviewing this project <br />will be chazged at the rate of $30.00 per hour. <br />In order for the processing of your application to cor�iinue, it will be necessary to provide the <br />Building Division with two complete new sets of drawings retlecting the corrections requested. <br />Upon resubmitta] of the drawings, your application erill be given priority and plan review <br />recommence. <br />All requirecl submittals shall be of sufficient detail and contain sufficient information to ensure that <br />the proposed structure wip be constructed in compliance with all adopted codes. <br />Sincerel , ���"^T <br />L� �� <br />e S Mcrall <br />Associate Enginecr/Building <br />15�1:cg/planck(5 <br />