My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
1028 BROADWAY 2016-01-01 MF Import
>
Address Records
>
BROADWAY
>
1028
>
1028 BROADWAY 2016-01-01 MF Import
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
1/23/2017 6:32:51 PM
Creation date
1/23/2017 6:32:04 PM
Metadata
Fields
Template:
Address Document
Street Name
BROADWAY
Street Number
1028
Imported From Microfiche
Yes
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
167
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
Plans for such system shall be submitted to the Fire Code O(ficial for review and approval <br /> prior to installalion. Submittal shall include cut sheels of all equipment intended for use. <br /> Appropriate trip lesls, wilnessed by a Fire Department Inspector, shall be performed, along <br /> with a certificate of completion, prior to final acceptance of lhe system. <br /> Fire alarm systems shall be installed according to NFPA Chapter 72. Installation of fire <br /> alarm components, including basic wiring, may not commence before plans are <br /> approved by the Fire Department Plan Reviewer. Fire alarm drawings must be <br /> professiunally rendered, in sufficient delail, and must be internally consis'ent. Riser <br /> diagrams must match installation plans and load calculations. Components must be listed <br /> and approved for use together. Changes to plans must include new drawings and <br /> calculations and must be approved by the Fire Department Plan Reviewer prior to <br /> instailati�n. Fire alarm installation is subject to field inspection by a Fire Deaartment <br /> Inspector. An approved set of plans and the Engineering and f'ublic Services Department , <br /> electrical permit must be present for any installation inspection. <br /> Fire alarm systems shall be installed under permit of the City of Everett Engineering and <br /> Public Services Department. Electrical inspections and appro��al are required prior to <br /> calling for acceptance tesis. Call (425) 257-8810 for permit informalion. <br /> The absence of working phone lines for the alarm system will be cause for <br /> postponing Fire Department inspection and testing and shall result in denial of <br /> occupancy. <br /> 12. Fire Suppression (Sprinklerl Svstem -An approved automatic suppression system shall be <br /> provided as required by City Ordinance No. 3021-07, Chapter 16.76, of the Everett <br /> Municipal Code. The system must include a mechanical water gong bell. <br /> Plans for any such system shall be submitted to the Engineering and Public Services <br /> Department(or examination and approval. Such plans shall include plans for the <br /> undergrour.d mains that will supply the sprinkler system. <br /> The lype of sprinkler to be installed will be determined by the Building Official. It may be an <br /> NFPA 13, NFPA 13R, or NFPA 13D system depending upon several factors. Sprinkler <br /> installation shall not begin without an approved and stamped set of plans from the <br /> Engineering and Pubiic Services Department. The Fire Department will also review the <br /> plans and shall (ield inspect the installation based only on approved plans that must be on <br /> site. Changes to plans must be approved by both the Engineering and Public Services and <br /> Fire Departments. <br /> Aboveground sprinkler piping shall be hydrostatically tested as established in NFPA <br /> Standard 13. Underground piping shall be hydrostatically tested and flushed as established <br /> in NFPA Standard 24 for private fire mains. LBe�ow-nround pipinn must be installed bv <br /> Washinqton State Patrol Licensed U�derpround Sarinkier line certified "U" <br /> installers. For further information, contact the State Fire Marshai's Office at (360) <br /> 570-3134 or contact the Everett Fire Department at(425) 257-8123.} All such tests shall <br /> be witnessed by a Fire Department Inspector. Call (425) 257-8124 to make an <br /> appointment for inspection. <br /> Contractors' materials and test certificates shal! be submitted to the Everett Fire <br /> Depariment prior lo issuance of any Certificates of Occupancy. <br /> iol�, <br />
The URL can be used to link to this page
Your browser does not support the video tag.