Laserfiche WebLink
, <br /> Egress <br /> 1. The daycare center doors should be shown on the drawings as operable from egress <br /> side without the use of a key, special knowledge, or effort, per IBC section 1008.1.9. <br /> 2. l ocks and latches cannot prevent the operation of doors in an E occupancy, per IBC <br /> section 1008.1.9.3, as amended by WA State. <br /> Accessibility <br /> 1. Alterations and a change of occupancy will require compliance with IBC sections <br /> 3411.4.2, and 3411.6, shown on the drawings. <br /> 2. Doors required to be accessible should have hard�vare that is opereble without tight <br /> grasping, pinching or twisting of the wrist, per IBC section 1008.1.9.1. <br /> These comments address building issues only. Revisions or additions may be required by other <br /> departments (such as Utilities, Planning or Fire). All required submittals must be of sufficient <br /> detail and information to ensure that the proposed structure wiil be constructed in compliance <br /> with all adopted codes. You can reach me directly to discuss this letter by e-mail at <br /> mhalev@everettwa.qov or by phone at 425-257-8813. <br /> Sin.:er � <br /> � _ <br /> Meg Hale NCARB <br /> Plans Examiner <br /> Cc h1rs. Lisa Woo, owner <br /> J <br /> 2/� <br />