Laserfiche WebLink
f _ _ _ <br /> Plan Check No: B-36887 <br /> September 22, 1992 <br /> Page Three of Three <br /> 14. The following items apply to the toilet room which must be accessible per Section 3106(k). <br /> A)The toilet must have a 32" minimum space in front (the hot water heater must be movedl. <br /> B) A clear space 60" in diameter must be provided within the toilet room. <br /> C)The toilet must be]ocated so that the centerline is 18" from the face of the grab bar (21" <br /> from face of wall) on the wall side and 42" clear space on the other side. (The 12vatory <br /> may project into the 42" clear space if the space un�er the lavatory is 29" minimum and <br /> if the lavatory edge is not less than I8" from the centerline of the toilet.) <br /> D)Insulate exposed hot water and drain piping under the]avatory. <br /> 15.Indicate the proposed heat source and provide the following minimum insulation values: <br /> Roof/Ceiling R-30 <br /> Exterior Walls R-11 <br /> Slab Edge R-7 <br /> Double Glazing for all windows <br /> 16. Reduce or revise the building lighting to conform to the maximum 1.7 watts per squa;e foot <br /> allowed. <br /> ln order for the processing of your applicadon to continue, it will iie necessary to provide the <br /> Building Department with two completepew sets of drawings reFlectine, the corrections requested. <br /> Upon re-submittal of the drawings, your application will be given priority and plan reviev <br /> recommence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to ensure that <br /> the proposed :tructure will be constructed in compliance with all adopted codes. <br /> Sincerely, <br /> ����� <br /> re S Mt`Fall <br /> Ass �ate Engineer/Building <br /> �sM:�`i�m�k.6 <br />� <br />�` <br />� <br />