x".i <br /> Plan Check No. 38915 & 38916 <br /> December 16, 1992 <br /> Page Two of Three <br /> 9. Plans do not show how the requirements of the Washington State Ventilation and Indoor Air <br /> Quality Code (V,I.A.Q.) are met. Show on plans; source specific ventilation, show all fan <br /> locadons and sizes. Whole house ventilation system, the whole house ventilation system <br /> shall su�ply outdoor air to all habitable rdoms through individual outdoor air inlets, forced- <br /> air heaung system, ducting or equivalent means. Spec�fy which type of system is to be used. <br /> 10. Provide size, species and grade of header at garage door. <br /> 11. Roof plan does not show; direction and spacing of trusses, girder trusses, or . ., species and <br /> grade of any sdck framing. <br /> 12. Provide typical wall section from footing to roof covering show all components including: <br /> finished grade, clearances in crawl space etc. <br /> 13. Call out minimum thickness of 3 1/2 inches concrete (floor slab-on-grade) reinforcement and <br /> moisture barrier, if any, on foundation plan. <br /> 14. Call out anchor bolt size and spaci�ig nn typical section. <br /> 15. Intermediate supports shown on foundadon plan aze not dimensioned. Dimension all pier <br /> blocks. <br /> 16. Specify opening size and locations of under floor ventilation equal to 1 square foot for each <br /> 150 square feet of under floor area/2516(c)6. <br /> 17. Provide typical wall section at garage wall. <br /> 18. Specify how ends of 4x8 girders in crawl space aze supported. Provide a de for girder <br /> splices over supports/2517(c). <br /> 19. Provide detail of intermediate supports showing a positive connection at posdbeam and <br /> foodng/post capable of resisting uplift and lateral displacement/2516(m). <br /> 20. Stub-out k4 rebar at 18 inches o.c, at concrete porch to resist differential settling. <br /> 21. Provide detail(s) of attic ventilation type, size and locadon. Show the required net area <br /> calculations assuming approximately 7596 of the vent area is net azea unless the actual net <br /> uea is given from the manufacturer/3205. <br /> 22. Provide 114 rebar at 48 inches o.c. vertical in foundation. <br />