�� <br /> Plan Check No. 389I5 & 38916 <br /> December 16, 1992 <br /> Page Two of 7'hree <br /> 9, Plans do not show how the requirements of the Washington State Ventilation and Indoor Air <br /> Quality Code (V.I.A.Q.) are met. Show on plans; source specific ventilation, show all fan <br /> locations and sizes. Whole house ventiladon system, the whole house ventilation system <br /> shall su�ply outdoor air to all habitable rooms through individual outdoor air inlets, forced- <br /> air heating system, ducting or equivalent means. Specify which type of system is to be used. <br /> 10. Provide size, species and grade of header at garage door. <br /> 11. Roof plan dces not show; direction and spacing of trusses, girder tnisses, or size species and <br /> grade of any stick framing. <br /> 12. Provide typical wall section from foodng to roof covering show alf components including: <br /> finished grade, clearances in crawl space etc. <br /> 13. Call out minimum thickness of 3 1/2 inches concrete (floor slab-on-grade) reinforcement and <br /> moisture barrier, if any, on foondation plan. <br /> 14. Call out anchor bolt size and spacing on typical section. <br /> 15. Intermediate supports shown on foundation plan are not dimensioned. Dimension all pier <br /> blceks. <br /> 16. Specify opening size and locations of under floor ventilation equal to 1 ,yuare foot for each <br /> 150 square feet of under floor azea/2516(c)6. <br /> 17. Provide typical wall section at garage wall. <br /> 18. Spccify how ends of 4x8 girders in crawl space aze supported. Provide a de for girder <br /> splices over supports/2517(c). <br /> 19. Provide detail of intermediate supports showing a posiGve connecdan at posUbeam and <br /> footing/post capable of resisdng uplift and lateral displacement/2516(m). <br /> 20. Stub-out A4 rebar at 18 inches o.c. at concrete porch to resist differential setding. <br /> 21. Provide detail(s) of attic ventilation type, size and location. Show the required net area <br /> calculations assuming approximately 7596 of the vent area is net area unless the actual net <br /> area is given from the manufacturer/3205, <br /> 22. Provide N4 rebar at 48 inches o.c. vertical in foundation. <br />