Laserfiche WebLink
• � �- <br /> 3. Regarding item N7 of the previous lett�:r. This applies to all doors on all levels. <br /> Specifications should also be added so the maximum transmitted temperature end <br /> point shall not exceed 450° F above ambient at the end of 30 minutes of the fire <br /> exposure specified in UBC Standard 7-2. <br /> Provide a response letter showing where each item in this correction letter is addressed <br /> on the plan set. <br /> Upon resubniital of thc drawings, your application will be given priority and plan review <br /> w�ill recommence. <br /> All required submittals shall be of sufficient detail and contain sufticient information ro <br /> ensuro that the proposed structure will be conswcted in compliance with all adopted <br /> codes. <br /> Sincerely, }'�1 �/� <br /> p � .. �.. <br /> Steve Miller <br /> Associate Engineer, P.E. <br /> SM:j�:b99�0-023 R Oi6 <br /> �Z <br />