My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
3003 W CASINO RD BLDG 40-22 2018-01-02 MF Import
>
Address Records
>
W CASINO RD
>
3003
>
BLDG 40-22
>
3003 W CASINO RD BLDG 40-22 2018-01-02 MF Import
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
9/13/2022 11:34:30 AM
Creation date
1/25/2017 1:46:23 PM
Metadata
Fields
Template:
Address Document
Street Name
W CASINO RD
Street Number
3003
Tenant Name
BLDG 40-22
Imported From Microfiche
Yes
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
1089
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
40-22/23 Building <br />Mezzanine Office Area <br />December 14, 1990 <br />[91OR&III111111"ll • a . <br />The building is construction Type II-N. The construction will be in accordance <br />with seismic zone 3. <br />The occupancy group for the new mezzanine is B-2. This conforms with the <br />existing use group. <br />The office area is to be constructed in accordance with Section 1716, 4 of the <br />1988 edition of the UBC. However, due to the need to maintain an "office" <br />environment, the perimeter walls will be constructed wit:13-1/2" metal studs and <br />two layers of 5/8-inch gypsum wall board on each side with resilient clips on the <br />office side. In addition, the perimeter walls are to have acoustical insulation to <br />give the desired STC rating. <br />j*A1fI1[Cj;m*111_► <br />The occupant load factor for an office space is 100 SF per person, [1988 edition <br />Atr/t of the UBC, Table No. 33-A]. The new mezzanine has an area of approximately <br />gait " 1,930 SF. Therefore the occupant load for exit calculations is 120 people. Two <br />ke'Go sc exits from the mezzanine. are required, at beast one of the exits e ust give direct <br />ri <br />and 51. Since the stair to the north extends down to an exit tunnel, the direct <br />access requirement is satisfied. Section 3303, (c), indicates that the two exits are <br />to be placed at a distance not less than one-half of the length of the maximum <br />overall diagonal dimension of the building or area to be served measured in a <br />straight <br />
The URL can be used to link to this page
Your browser does not support the video tag.