Laserfiche WebLink
COLD WATER CROSSTIE <br /> EVERETT SITE, SOUTH COMPLEX <br /> JOS NUMBER 920553 ' <br /> A. OBJECTIVE <br /> Add an 8-inch domestic water connAction from the end of the <br /> 12-inch main off Airport Road to the existing 6-inch supply <br /> line for Buildings 45-03 and 45-06. This crosstie will � " <br /> become the primary supply line for those two buildings and <br /> for the Field Steam Plant, Building 45�07, now under <br /> construction. it wi7.1 also be a secondary source of City <br /> Water to the rest of the South Complex. At the present time, <br /> the only source is a 10-inch line across the freeway bridge <br /> from the North Complex. - • � ,' <br /> B. SCOPE OF WORK <br /> Refer to Technical Specification P-1046D <br /> 1. Install approximately.350 lineal feet of 8-inch, cement- <br /> lined, ductile iron pipeline around the South side of .the <br /> 45-06 Building. - <br /> 2. Pressure-test the new 1 'ine to 100 psig. <br /> 3 . Connect the new line to the existing 12-inch valve •at the <br /> end of the new supply line located near the southeast <br /> corner of Bldg. 45-06. , ' <br /> 4. Disinfect and flush the new line according to City of <br /> Everett domestic water supply requirements. <br /> 5. Connect the new line into a valved tee inserted into the <br /> existing 8-inch supply line for Bldg. 45-03 at a point <br /> west of Bldg. 45-06. <br /> C. DRAWING REFERENCE <br /> 45-04 Shee.t Co�2 REV.E <br /> RECOMMENDED CONTRACTORS <br /> Clemens & Jaurez rV (� �� <br /> Deeny construction � � � � � � J {5 <br /> Lumpkin Construction � <br /> U U CCC C 3 �� ,, <br /> Prepared by: C. F. Heilbronner C '� �' G EVERETT <br /> T-6153 742-5213 dldR. Parmit Counter <br /> November 17, 1993 <br />