AW <br />Page 2 <br />LZWM�;.� <br />Each conductor was tested individually with cables not under <br />test grounded. The cables were energized and leakage <br />current monitored to shield and ground. Tests were <br />performed in accordance with customer supplied test <br />specifications. <br />4.1 Step Voltage Test <br />The cables were raised in 8kV steps to a maximum test <br />potential of 64kV. DC leakage current was monitored at <br />each step after a stabilization time of one (1) minute, <br />consistent with system charging current. <br />4.2 Absorption Tests <br />The cables energized at the 64kV level were monitored <br />for leakage current at half -minute intervals for the <br />first minute and then at one minute intervals for a <br />total of 15 minutes. <br />4.3 Voltage Decrement Test <br />At the completion of the absorption test, the potential <br />was removed from the cables and the voltage and time <br />monitored as the cable discharged through its <br />dielectric volume resistance. <br />5.0 RESULTS <br />5.1 The test results and evaluation indicate the cables are <br />satisfactory for energization. <br />Submitted by, <br />✓Jim Pallansch <br />Field Technician <br />