Laserfiche WebLink
- --�- <br /> Page 4 <br /> 6. 2 vis�al inspection <br /> The equipment was visually inspected with particular <br /> attention to the following areas: <br /> Use of "approved" components. <br /> Wiring ampacity, <br /> Grounding <br /> Wiring methods. <br /> Guarding of live parts. <br /> Damaged components. <br /> General engineering practices. <br /> 7.0 �pUIPMENT DIBCREP IEg x �p RlPTTf1NB <br /> 7. 1 15kV Switch Assemblies <br /> 7. 1. 1 The hinged door enclosinq the non-fused switch on <br /> circuit 1-2 in both Substation 45 and 46 is not <br /> provided with the required interlock devices to <br /> prevent openinq the door when the ewitch is in the <br /> closed position. An interlock shall be installed <br /> to prevent opening each door when its respecttve <br /> switch i.s in the closed position. <br /> Reference: ANSI/IEF. C37.20. 3 Par. 6.5. 1 <br /> Report.ed: 5/3/93 <br /> Corr�ot�ds The required interlocks have been <br /> installed on each door to prevent opening when the <br /> switch is closed. <br /> v�rifi�d: 5/12/93 <br /> 7.1. 2 The load aide of any of the awitches inspected can <br /> be enerqized when the awitch is in the OPEN <br /> position due to the "dual feed" bus assembly on the <br /> load side of the awitches. The door interlocks <br /> provided on the non-fused sw:tcl� (1-2) at each <br /> substation does not prevent opening the door when <br /> the load aide of the switch is energized from <br /> another source. A cautionary markinq ahall be <br /> installed at each non-fused ewitch statinq the <br /> following or equivalent: °WARNING - Risk of <br /> Electric Shock. Load eide of switch may be <br /> energized when ewitch ia in the open poaition. <br /> Diaconnect all power supplies before servicing. �� <br /> Reference: ANSI/IEEE C37.20. 3 Par. 6. 5. 1 <br /> Reported: 5/3/93 <br /> Corteateds The required cautionary markings have <br /> been installed on each door. <br /> Verifiedi 5/12/93 <br /> i <br />