Laserfiche WebLink
0 <br /> ` 3 <br /> K o > <br /> r � 9 g <br /> y �' e a <br /> � V a z° <br /> A 30 � Not Approved 11/26/02 - Provide revised drawings locating the toilet paper <br /> dispensers next to the water doset and not on the back wal! as shown on Sheet 7.03 <br /> Elevations 8 &9 and Sheet 7.04,Elevations 1, 2, 3, & 5. <br /> WAC 246-?2G-405(2)(i), a�id WAC 246-320-345(1) <br /> Approved Ol/13/03-Drewings revised to show toilet paper dLs;pensers next to <br /> the water closeG <br /> A 31 � Not Approved 11/26/02- Provide revised drawings identifying the use of the rooms <br /> east of Grid 6B if they will no longer be providing obstetric services. If they are <br /> unassigned, then they will be wnsidered slorage rooms with the nced for.s one-hour <br /> occupancy sepazation including one-hour rated doors. WAC 246-320-SO:i(2)(b), <br /> WAC 246-320-525(2), and Section 302.4 and Table 3-C, Uniform Building Code <br /> Approved OV13/03-Revised drawings note that these rooms 8381 B384,B399 <br /> and rooms east of Grid 2B will be used for oftices. <br /> A 32 0 Not Approved I 1/26l02 - Provide revised drawin�s coordinating floor plan Sheet <br /> A23BE and Interior Elevation Sheet AZ02 for Patient Bath B352 and B353, and <br /> between Sheet A23C and Interior Elevation Sheet A7.05 for Patient Bath C326. <br /> Approved 0 U13/03- Revised drawings show Ooor plans and interior elevattons <br /> coordinated ior these rooms. <br /> A 33 0 Not Approved 11/26/02- Provide revised drawings showing that the grab bar at the <br /> side of the water closet in Patient Bath B353,Toilet B347 —if patient accessible, <br /> Patient Toilet B304, and all patient room toilets in Wing 3C extends at least 18 <br /> inches beyond the water closet. WAC 246-320-525(7)(h)(ii)(B) <br /> Approved Ol/13/03 - Revised interior elevations Sheets A7.03,A7.04,and A7.05 <br /> show 18-inch dimension added. <br /> A 34 0 Not Approved L 1/26/02-Provide revised door hazdw:ue for poor 8355. Hardwane <br /> Group#13 dces not provide for self-closing of bolh doors as is required for a rated <br /> door assembly opening to the corridor. WAC 246-320-525(2), and Section <br /> 10043.43.2.1, Uniform Building Code <br /> Approved Ol/13/03- Revised Door Schedule notes thet both doors tor poor <br /> B355 assembly to Linen B355 in Corr.B301 shall be equipped with a closer. <br /> A 35 x❑ Not Approved 11/26/02 -Fcovide revised door hazdware for poors C336,C337 and <br /> C339. Hardware Gruup#14 dces not provide for a rated door assembly with closers, <br /> positive latcl�es, etc. WAC 24G320-525(2), and Section 10043.4.3.2.1, Uniform <br /> Buildiug Codc <br /> Pzge 9 of I I Plan Review Comments for Project M 6345 <br /> Review Kcy: A=Arehirea P=Pire&Li(e Sefety S=Saniiarian M=Mxhanical/Elatrical C=Conforcnce Nole <br /> ��f <br />