• � <br /> � C� � <br /> ~ '� 3 � <br /> > <br /> � � � z <br /> z" u° a z' <br /> ?�5.1 � Appro�ed Ol/13/03 • Door Hardware Schedule revLsed to note that Dours C336 <br /> and C339 shall be twenty minute rated assemblies. <br /> 35.2 � Not Approved Ot/13/03 - Alcove C337 shall not be used fur linen storage unless this <br /> area is sepazated from the rated corridor by ratcd door and wall assemblies. <br /> Approved 07/20/03—Revised Sheet A2.3C has chenged the title of this alcove <br /> from linen storage to equipmenl storage. <br /> A 36 � Not Approved I 1/26/02 - Provide revised drawings and door sciredule showing each <br /> patient room door with a minimum 3'-]0"clear opening without the need to activate <br /> the breakaway feature. WAC 246-320-525(2)(d)(i) <br /> Response states that an exemption request has been submitted for this item. <br /> Approved OT/06/03—Per interpretation,door meets intent of rule,no e-empHon <br /> required. <br /> /1 37 � Not Approved 11/26/02- Provide revised door schedule showing that the sliding <br /> glass patient room doors opening to the rated corridor in Wing 3C are tight fitting, <br /> smoke- and draft-control assemblies with positive latches. WAC 246-320-525(2), <br /> and Section 1007.5.4(6), Uniform Building Code <br /> Approved OU13/03- Revised Door Schedule on Sheet A8.04 added note for the <br /> doors opening to the corridor be tight 6tting,smoke-and draf�t-control <br /> assemblies with positive IatcMes. <br /> A 38 O Not Approved i l/26/02 Provide revised drawings removing the non-rated cabinets <br /> from corridor C336 or explain how they aze allowed by the code. <br /> WAC 246-320-525(2), and Section 1004.3.4.3.1, UniCorm Building Code <br /> Approved Ol/13/03- Revised drawings show non-rated cabinets removed from <br /> Corridor C336. <br /> A 39 0 Not Approved I 1/26/02-Provide revised drawings providing at least a 4'-0"cleaz <br /> spacc along both sides of the patient bed in Patient Room C312 and C346. An <br /> exemption may be requested explaining why it is to the patients henefit that the <br /> conf guration shown with a struclural column and power column preventing access <br /> to the patient from one side of the bed. WAC 246-320-725(3)(c)(i) <br /> 39.1 Not Approved 01/13/03 - Revised Sheet A0.61S does not provide a dear passage for <br /> a transition ftom the side clearance to the end clearancc requirements. Clearance <br /> from the power column and structural column are not thc only issues but also ho•.v <br /> the wall of the adjoining patient room and wall of the monitoring station encroach <br /> into required maneuvering space. <br /> Approved 03/21/03-Exemption granted,see CRS #6345-005. <br /> Pagc 10 of I 1 Plan Review Comments for Project#6345 <br /> Rer�ew Kcy: A=A¢hitecl F=Pire&Lde Safe�y S=Sanitanan M=Mechanical/ElecMcal C=Conferente Note <br /> `C.J' <br />