s_ <br />Page 4 <br />18 May 1993 <br />Mr. Warren Burns . <br />BUILDING LIFE SAFETY SYSTEMS <br />ITEM 4: LOCATION OF STANDPIPES <br />Code Requirement i 1tp�,�>�!� <br />G� <br />71 <br />Per sectlon 5,3.2 of NFPA 1 j ' <br />Class [.systems shall be provided with 2 1/2 'hos)connections at the <br />following locations: (A_ <br />A. At each (idarmediate landing between flood, levels in every <br />required exit stairway. - <br />B. On each side of the wall adjacent to exit openings of horizontalCv <br />exits.. <br />C. In each exit passageway at the entrance from building areas in <br />to the passageway. 1 • • <br />D. In covered mall buildings at the entrance to - each exit <br />passageway or exit corridor, and at exterior public.' entrances <br />"to the mall. <br />E. At the. highest landing -of stairways with stairway access to a <br />roof and on the roof where stairways do not access the roof. <br />F. Where the most remote portion of a nonsprinklered floor or <br />story exceeds 150 ft of travel distance from a required. exit or <br />the most remote portion of a sprinklered floor or story exceeds . . <br />200 ft of travel distance from a required exit, additional hose <br />connections shall be provided, in approved locations, where <br />required by the local fire department. <br />Proposed System Design• <br />Flnors 2-10 will be provided with fine standpipe located in each enclosed <br />stairway. All hose conneEons will be in accordance with the above <br />applicable re rements. <br />A I A [ U i <br />'S'd siNuiinswoD SnDuau WWO :60 E6, 01 d3S <br />