Laserfiche WebLink
3. Comment: The locations of the tactile exit signs should be shown on the plans. <br /> Section 1011.3. <br /> BNH Response: Please re(er to keynote 1.3� or sheet A1.0. <br /> 4. Comment: The emergency power supply and locations for the means of egress <br /> iliumination should be shown on the plans. Seclion 1006.3. <br /> BNH Response: Please refer to keynote 2.9 on sheet A2.0. <br /> 5. Comment: Doors 100A, 104A, 1048 & 1146 should be provided with panic <br /> hardware. Seclion 1008.1.9. <br /> BNH Response: Panic hardware is now noted on the door schedule. <br /> Accessibflitv: <br /> 1. Comment: Areas of evacuation assistance are not required for lhe change of <br /> use—we <br /> wili leave this for your discretion. Section 3409.3. <br /> BNH Response: The area of evaa�ation has been removed. <br /> 2. Comment: The flush controls for the accessible toilets should be shown away <br /> from the <br /> near wall. ANSI Section 604.6. <br /> BNH Response: Please refer to elevalions 19 and 24 on sheet A7.1. <br /> 3. Comment: The accessible toilets (seat heighls) should be shown between 17-19 <br /> inches high. ANSI Section 604.4. <br /> BNH Response: Please refer to lhe water closet�' �:ail on sheet A7.1. <br /> Sincerely, <br /> BOTESCH, NASH & HALL ARCHITECTS, P.S. <br /> ��$�. <br /> Chris Raef <br />