Laserfiche WebLink
, � � <br /> Tuny Lee <br /> Marclz 7, 2003 <br /> Page 3 <br /> 6. The centerline of the toilets should be shown at 18" from <br /> tlie closest wall. The flush control should be shown on the <br /> opposite side of the tank from the near wall. Section <br /> 1106.11 .5.1 . <br /> •'Revised, see sheet A-5 toilet room elevations. <br /> 7. The height of the toilets should be shown on the plans ;17"- <br /> 19"). Section 1106.11 .5.2. <br /> wwRevised, see sheet A-5 toilet room elevations. <br /> 8. The cabinetry of the lavatories should be relocated such that <br /> they do not impinge upon the minimum 60" turning radius in the <br /> toilet rooms. Section 1106.11 .2. <br /> "'Revised, see sheet A-2 toilet room plans. <br /> ENERGY: <br /> 1 . The plans should note the energy code compliance path and <br /> requirements for the envelope. <br /> ""Energy compliance etc. will be included with the <br /> mechanical and electrical deferred submittals. <br /> Should you have any further questions or comments please call. <br /> Thank you for your time accorded me in our telephone calls and <br /> your expedient processing of our permit. <br /> Sincerely, <br /> i <br /> ����-E �._�,������'--��- <br /> �, ,_�,i <br /> William A. Finley <br /> WAF/dja <br /> 33 <br />