My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
5830 EVERGREEN WAY 2016-01-01 MF Import
>
Address Records
>
EVERGREEN WAY
>
5830
>
5830 EVERGREEN WAY 2016-01-01 MF Import
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
2/9/2017 9:34:53 PM
Creation date
2/9/2017 9:33:51 PM
Metadata
Fields
Template:
Address Document
Street Name
EVERGREEN WAY
Street Number
5830
Imported From Microfiche
Yes
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
396
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
� <br /> C:� �. <br /> 39. PREMISE IDENTIFICATION AND ALL REQUIRED FIRE DEPAI�TMENT <br /> ACCESS ROADS� AND FIRE HYDRANTS MUST BE IN SERVICE PRIOR TO <br /> COMMENCEMENT OF CONSTRUCTIQN OF BUILDIN�S. <br /> 40. A portable fire exCinguisher with a minimum UL rating of ZA:10-B:C must be <br /> provided within 7a feet travel distance on each floor of all portion� of each <br /> bwiding during ccrostruction and prior to occupancy. <br /> 41. M approved autamatic fire detection system must be provided as required by <br /> City Ordinance Na. 1902-92, Chapter 16.76 of the Everett Municipal Code. <br /> Fire alarm systems shall be instailed according to NFPA Standard 72. <br /> 42. Plans for such system must be submitted to the Fira Marshal for review and <br /> approval prior to installation. Submittal shall inGude cut sheets of all equipment <br /> intended for use. Appropriate trip tests, witnessed by a Fire Department <br /> inspector, must be performed prior fo final acceptance of the system. <br /> Fire alarm systems must be installed under perrt�it of the City of E.verett Building <br /> Oepartment. Electrical inspections and approval are required p��or to calling for <br /> acceptance tests. Call 259-8810 for permit information. <br /> 43. Fire Suppression (Sprinkler) System -An approved automatic suppression <br /> system shall be provided as required by City Ordinance No. 1902-92, Chapter <br /> 16.76 of the Everett Municipal Code. <br /> Plans for any such system shall be submitted to the Building Department and the <br /> Everett Fire Department for examination and approval. Such plans shall include <br /> plans for the underground mains that will supply the sprinkler system. <br /> Above ground sprinkler piping musE be hydrostatically tested as established in <br /> NFPA Standard 13. Underground piping must be hydrostatically tested and <br /> flushed es established in NFPS Standard 24 for private fire mains. All such tests <br /> must be witnessed by a Fire Department inspector. Call 259-8710 to make an <br /> appointment for inspection. <br /> As of January, 1991, sprinkler system permits are issued by the Building <br /> Department. Plan review fees are assessed by the Building Department. No fee <br /> is assessed by the Fire Department. <br /> Contractors' materials and test certificates must be submitted to the Everett Fire <br /> Department prior to issuance of any Certificates of Occupancy. <br /> Call 259-8720 for more information. <br /> Please call 259-8726 for further informetion. <br /> 44. The City of Everett prohibits outdoor buming. Therefore, outdoor buming for the <br /> purpose of disposing of construction debris or rubbish will not be permitted. <br /> 45. Fire hydrants and access roads must be in service prior to commencement of <br /> construction. <br /> ; <br /> to <br />
The URL can be used to link to this page
Your browser does not support the video tag.