Laserfiche WebLink
�- <br />i <br />An area separatiai wall between the offices and storage area appears unnecessary. <br />Buildings "B" and "O" could be combined and still meet allowable area <br />requirements. Detail 3, sheet 6 would need revisions for it to comply as an area <br />separation wall. <br />The live load for which che upper level was designed to support shall be posted <br />throughout with durable metal signs located in conspicuous locations. Please add <br />this requirement to the drawings. This loading must agree with the design criteria <br />shown in the general notes of sheet 6 and the structural notes of sheet S1 (they <br />don't agree). <br />9. Th� guardrail detail 5/6 appears incomplete. <br />Prepare a response letter showing where each item in this letter is addressed on the plan <br />set. <br />Upon resubmital of the drawings, your application N�ill be given priority and plan review <br />will recommence. <br />All required submittals shall be of sufficient detail and contain sufficient information to <br />ensure that the proposed structure will be conswcted in compliance with all adopted <br />codes. <br />Sincerely, j � � I � � <br />. <br />���� � <br />Steve Miller <br />Associate Engineer, P.E. <br />sM:i����-0so <br />