Laserfiche WebLink
CHECK NEW CONDITION WITH ITEM 3-BDT1200L6C WEIGHT= 14951bs <br />UNITS �NIDTH = 42" UNITS LENGTH = 74" <br />MUST _�NGAGE AT LEAST (2) 2X8 ROOF 1015T <br />USE SLEEPER TO TRANSFER LOADS <br />ASSUME LOAD IS TRANSFERRED @ ENDS OF UNIT BY SLEEPER <br />#OFENDS=2 <br /># OF JOISTS USE TO TRANSFER = 2 <br />P=1495/2/2= 373.75 ibs <br />TOTAL LOAD = EXISTING + NEW CONDITON = 296 + 373.75 = <br />Mall= 13.24 k-ft <br />M=P * a 0.61 k-ft <br />Mall »> M OK <br />CHECK NEW CONDITION WITH ITEM 4-dDT1500L6C WEIGHT= 1442 Ibs <br />UNITS WIDTH = 42" UNITS LENGTH = 75" <br />MUST ENGAGE AT LEAST (2) 2X8 ROOF JOIST <br />USE SLEEPER TO TRANSFER LOADS <br />ASSUME LOAD IS TRANSFERRED @[NDS OF UNIT BY SLEEPER <br /># OF ENDS = 2 <br /># OF JOISTS USE TO TRANSFER = 2 <br />P=1442/2/2= 360.50 Ibs <br />TOTAL LOAD = EXISTING + NEW CONDITON = 296 + 360.50 = <br />Mall= 13.24 k-ft <br />M=P * a 0.00 k-ft <br />Mall »> M OK <br />CHECK NEW CONDITION WITH ITEM 5-BDTO800L6C WEIGHT= 1183 Ibs <br />UNITS WIDTH = 37" UNITS LEN�TH = 64" <br />MUST ENGAGE AT LEAST (2) 2X8 ROOF JOIST <br />USE SLEEPER TO TRANSFER LOADS <br />ASSUME LOAD IS TRANSFERRED @ ENDS OF UNIT BY SLEEPER <br />#OFEND5=2 <br /># OF JOISTS USE TO TRANSFER = 2 <br />P=1183/2/2= 295.75 Ibs <br />TOTAL LOAD = EXISTING + NEW CONDITON = 296 + 295.75 = <br />Mall= 13.24 k-ft <br />669.75 Ibs <br />656.50 Ibs <br />591.75 Ib5 <br />