Laserfiche WebLink
� I <br /> most cases, botl� sides of the a.:cess road shall be marked. Where loug drives a��e to be marked, the <br /> repeti�ions shall alternate sides of the dri��e. <br /> c. Marking shall also indud� U�c addition of inetal signs st.tting '"d0 PARKING - FiRC LANE- <br /> TOW AWAY ZONE' to be installed at intervals or loc.iions des�gn^red by ti�e !im. code official. <br /> The si�ns shall be approximately 12 inches in width and 1R inci;es in t�e �t��� ���c': '.�,� �; c;:,i l�tters cu a <br /> white background. Metal signs shall be installed on eithe. 2-i�1Clt me:a! :•:'•'_•. �'��' �;ri"a[e property or <br /> treated 4-inch by 4-incl� wood posts for public propert}� and shal( be loca[ed s� that the bottnm of the <br /> sign is a minimum of 7 feet above the curb. Where lire lanes are adjacent to buildiugs or structures <br /> and wl�en approved or directed by the tire code official, the signs may be placed on the face of the <br /> building or structure. <br /> E Where directed by the fire code officiat, specific areas shall be designated and those areas are to be <br /> marked with diagonal striping across the widQ� of the fire lane. Diagonal marking shall be used in <br /> conjunction �vith painted curbs and/or edge striping and shall run at an angle of 30 to 60 degrees <br /> from one side to the other. These diagonal lines shall be in red traffic paint, paralfel with each other, <br /> at least 6 iriches in width and 24 inches apart. Lettering shall appear as above. <br /> 5. Securitv �ence - Any security fence erected arom�d the construction site shall be located so as to not <br /> obstruct any cxisting hydrant, tirc protection equipment, or Fire Department access. [f Fire <br /> Department access is obstructed, gates or other openings shafl be provided for access. <br /> G. Premise [dentification - Premiscs shall he cleariy identified by the correct address at the street entry. <br /> f3uiWings siudl bc clearly idcntified so as to be visible and legible from the access road. Individual <br /> aparUncnts and suites, wherc applicablc, shall be dearly ai�d legibly identiticd 1'rom the access road. <br /> ?. Fire Hvdrants - Locations as plaimed are acceptable. <br /> 8. Qased upon 11,587 square feet of Type V-B, sprinklered consu•uction, the fire tlow reyuirement is <br /> I,S00 gpm. <br /> 9. Pire Sunnression (Snrinkler) System - An approved automatic suppression system sl�all be provided as <br /> required by City Ordinauce No. 1902-92, Chapter 16.76, of the Everett Municipal Code. The system <br /> �uust include a meclianical water gong bell. Plans for any such system shall be submitted to the <br /> I3uilding Dcpartment tbr exaiuination and approvaL Such plans shall include plans for the <br /> underground mains that will supply Utc sprinkler system. The type of sprinkler to be installed will <br /> be determined by U�c I3uilding OfticiaL It may be an NFPA 13, NFPA 13R, or NFPA 13D system <br /> depending upon several factors. Sprinkler installatiou shall not begin w�thout an approved and <br /> stamped set of plans from the [3uilding Department. The Fire Department will also review the <br /> plans and shall Gcld inspect the installation based only on approved plans that must be on site. <br /> Changcs to plans must be approved by bodi the Building and Fire Departments. Aboveground sprinklcr <br /> piping shall Ue hydrosta[ically tested as established in NPPA Standard 13. Underground piping shall <br /> be irydrostatically tested and (lushed as establislied in NFPA Standard 24 for private fire mains. <br /> (I3clow-eroimd nipine must be iustalled bv �Vashin�ion State Patrol Licensed Underaraund <br /> Sprinklcr line certified "U" installers. For further information, contact the State Fire Nfarshal's <br /> Office at (360) 570-3134 or contacf the E��erett Fire llepartment at (425) 25'1-8123.) All such tests <br /> shall Uc witnessed by a Pire Deparnnent inspccror. Call (425) 257-8124 to make an appointment tbr <br /> �tp ]. <br /> ��� <br />