Laserfiche WebLink
July 14, 1972 <br />Luther Child Center <br />Page Five <br />Staff quarters <br />l.. The windows in staff bedrooms do not meet the requirements of Section <br />1405, UBC. We figure 18 square feet is required with � to be operable. <br />2. We highly recommend an exit door directly to the exterior from corridor <br />V210 near Room V208. <br />3. Provide portable fire extinguishers, <br />Shop BuildiiLi; 30't <br />1. The shop is a hazardous area and door #2 should swing out, <br />2. Provide portable fire extinguisher. <br />Laundyy and Ironing <br />1. Provide fire extinguishers. <br />Administration <br />1. The folding curtain can not be completely closed without providing a <br />sw.ingirg door directly to the exterior or blocking the track permanently <br />to permit a-3 foot opening or providing a swinging door at the north <br />end through the curtain. <br />2. Corridors ii424 and 1420 shall be not less that 44" wide if the occupant <br />load from all rooms opening to this corridor exceeds 10 as required by <br />Section 3304 (A-B). We recommend 44" regardless of the above minimum. <br />al.ng door #2 in direction of egress. Also see item i,6 below, <br />3. Door 7#6 from Office 1#501 to stair shall be 46" wide and swing into the <br />stair. <br />4. Provide exit illumination and exit signs as required by Section 331.2 UDC, 1970. <br />5. Provide 2' gallon water type fire extinguishers in corridors and B-C type <br />in kitchen as required by Standard #10, NFPA. <br />6. Exit corridors #422, #423 and #425 shall meet 1-hr. construction as <br />required by Section 3304(g) UBC, 1970. <br />All doors opening from rooms or areas to this corridor shall comply <br />with 3304(h). <br />