Laserfiche WebLink
C <br />Pa9e l of 3 <br />s/kathy/heilmaNC�llu-001 (6011 Mming) <br />Octaber 11, 2011 <br />26. The section drawings on Sheet A7 and the details on Sheet A8 show raised heel <br />trusses. Provide detail for transfer of loads from roof diaphragm to the exterior walls <br />(show blocking capable of transferring roof loadl. <br />27. The section drawings on Sheet A7 do not show adequate ciearance under beams and <br />joists in crawl space, but shows vapor barrier underground. <br />28. Section 3 on Sheet A7 shows a concrete porch and steps but there is no door on the <br />north side of the house. <br />Please prepare a response letter showing where each item in this correction letter is <br />addressed on the plan set. <br />Upon resubmittai of the drawings, your application will be given priority and pian review will <br />recommence. <br />All required submiltals shall be of sufficient detail and contain sufficient information to ensure <br />that the proposed structure will be constructed in compliance with all adopted codes. <br />Sincerely, <br />�'� ��„�— <br />Jeff Heilman <br />Development Technician <br />425-257-8976 <br />Email: iheilman ci.everett.wa.us <br />/ -_ �i <br />5/kathy/he�dman/CI110�001(G�tl Fleming) � j <br />�i � <br />j. <br />