basic wiring, may not commence before plans are approved by the Fire <br /> Department Plan Reviewer. <br /> Fire alarm drawings must be professionally rendered, in sufficient detail, and <br /> mLst be internally consislent. Riser diagrartr; must match installation plans and <br /> luad calculaUons. Components musl be lisled and approved for use logeiher. <br /> Changes to plans must include new drawings arzd calculaUons and rtwst be <br /> approved by the Fire Department Plan Reviewer prior to insfallation. <br /> Fire alarm instailation is subJect lo field inspeclion by a Fire Departmenl <br /> Inspector. An approved set of plans and lhe Building Department e�edrical <br /> permil musl be present for any installaUon inspeclion. <br /> Fire alarm systems shall be installed under permil of the City of Everett Buflding <br /> Deparlment. Eleclrical inspeclions and approval are required prior lo plling for <br /> acceptance lesis. Call (425)257-8810 for permil in(ormation.The absence of <br /> working phone lines for the alarm system will be cause for postponing fire <br /> department inspection and tesling and shail result in deniai of oc:cupancy. <br /> 56. An approved automatic suppression sys'em shall be provided �s required by City <br /> Ordinance No. 1902-92, Chapler 16.7fi, of Ihe Everetl Nunicipal Code. The <br /> system must include a mechanical water gong bell. Plans (or any such system <br /> shali be submitled to the Building Department for examination and approval. <br /> Such plans shail indude plans for thr underground mains that will supply the <br /> sprinkler system. The type of sprinkler to be mstalled will be determined by the <br /> Building O�cial. Il may be an NFPA 13, NFPA 13R, or NFPA 13D system <br /> depending upon several Tactors. Sprinkler installation shall not begin wfthout an <br /> approved and slamped set oi pla�is (rom the Building DepaAment. The Fire <br /> Department will also ieview the plans and shall field inspect Ihe installatlon <br /> based only on approved plans that must be on site. Changes to plans must be <br /> approved by both Ihe Building and Fire Departments.Aboveground sprinkler <br /> p�ping shall be hydrostalically fested as establfshed in NFPA Standard 13. <br /> Underground piping shall be hydrostatically tested and ilushed as established fn <br /> NFPA Standard 24 for privale fire mains. {Below-qround �idna must be installed <br /> by Washinaton State Patrol I icensed Underoround arinkler line cert�ed " " <br /> installers. For further informalion, contad the State Fire Marshal's Offlce at (360) <br /> 570-3134 or contacl the Everett Fire Department at (425)257-8123.) All such <br /> tests shall be witnessed by a Fire Depertment inspector. Cali (425) 257-b124 to <br /> make an appointment tor inspection. Contractors' matenals and test cerliflcates <br /> shall be submitted to the Everett Fire Depertment prior to issuance of any <br /> Certi(icales of Occupancy. <br /> 57. A ventilating hood and ducl system with an approved automatic fire-extinguishing <br /> system shall be provided in accordance with the Mechanical Code for <br /> commercial-lype food heat-processing equipment that produces grease-laden <br /> vapor. <br /> 58. For commercial cooking occupancies, a K-iype fire extinguisher must be installed <br /> wilhin 30 feel of the grill and deep(ryer. <br /> 59. Slandpipe systems shall comply with NFPA 14. <br /> 60. Conslruction and demolition of buildfngs shall be in compliance wilh the <br /> provisions of the 2003 Inlematfonal Fire Code, Chapler 14. <br /> 22/��� <br />