( <br />Plan Check No. 60674 <br />December 17, 1998 <br />Page 2 of 2 <br />( <br />7. Plans should indicate the requirement for fire dampers where fan ducts penetrate one-hour <br />ceiling/tloor assembiies. See UBC Section 713.11.4. <br />8. The main level units are required to meet the requiremenu for Type B accessible dwelling <br />units. See UBC 1103.1.8.2 and 1106.27.1, State Amendments. <br />9. The minimum width on an accessible parking spot is 13 feet per UBC Section 1107.2.2. <br />Please revise. <br />Prepare a response letter showing where each item in this correction letter is addressed on the plan set. <br />Upon resubmittal of the drawings, your application will be given priority and plan review will <br />recommence. <br />All required submittals shall be of sufficient detail and contain sufficient information to ensure that the <br />proposed stru re will be constructed in compliance with all adopted codes. <br />Sincerely, �. �--- <br />// <br />Steve Miller, PE <br />Associate Engineer <br />SA1:juEycldicykk.6� <br />