Laserfiche WebLink
� <br /> , � i <br /> Ltr. D. Klappenbach (B0202-025) <br /> Apri18, 2002 <br /> Page 3 <br /> Construction <br /> I. The listings for the fire-resistive tloor/cciling and roof/ceiling assemblies should be <br /> shown on the plans. Note that the 9' wide canopy is also a roof/ceiling assembly. <br /> Sec[ion 703.1 <br /> 2. Sprinicler note: The ceiling creates a void space in the roof. As plywood decking is <br /> used, the space is not entircly noncombustible and sprinklering the roof/ceiling void <br /> will result per NFPA 13. <br /> 3. Lis[ings should be provided for all fire-resistive wall asscmblies shown. Section 703.1 <br /> 4. The penthousc uver the stairs should bc of non-combustible construction. Section <br /> 1511.4 <br /> 5. It should be shown that the high-tension cables used for guard railing in Staiiway #1 <br /> will not detlect such that a 4" diameter sphere may pass through. Section 509.3 <br /> C. Th� glazing types should be keycd into Ihe rclitc schedule. <br /> Exiting <br /> 1. Panic hardware should be provided on Door #102 as it is an exit from the comdor <br /> serving Stair#2 and the A-3 Occupancy above. Section 107.2.5 <br /> 2. Panic hardware shoufd be provided on Door#123B as it is an exit access door from an <br /> H-2 Occupancy. Sections 1007.4.5 & 1d03.3.1.1 <br /> 3. Unless the elevator shaft is pressurized in accordance with Section 905, an elevator <br /> lobby should be provided at both Floors where the elevator opens into the wrridors. <br /> Section 1004.3.4.5 <br /> 4. Corridor doors 216 should be minimum self-closing, 20-minute assemblies. Section <br /> 1004.3.4.3.2.1 <br /> 5. All corridor doors should be specified to listed with an "S" labzl. Section <br /> 1004.3.43.2.1 <br /> G. Lxit signs should be shown at each exit or exit access door leading from the H-2 �I <br /> Occupnncy. Sections 1003.2.8.2 & 1007.4.3 <br /> �y <br />