Laserfiche WebLink
_ _ __-=- -- - - - -- -- <br />' 10. The exhaust far, is required to 6e hinged in accordance with IMC 506.5.3 Please <br />include. <br />11. The plans should include the requi-ement for a leak test in accordance with IMC <br />506.3.2.5. <br />12. The plans should include the requirement for a fire suppression system which will <br />require a separate permit. <br />If you have any questions, please call me at 925-257-7264. <br />Upon resubmittal of the drawings, your application will be given priority and pian review will <br />recommence. <br />All required submittals shall be of su�cient detail and contain sufficient information to ensure <br />that the proposed structure will be constructed in compliance with all adopted codes. <br />Sincerely, <br />� <br />Steve Miller <br />Associate Engineer <br />5�ICommoa:Cl�ricahc�till� :M CM.� I I��: ) Gu I.tdl N'n10oc <br />