Laserfiche WebLink
iO Lawrence T. Erickson, ising Conservacion <br /> FAo" L. J. Dougherty :�� <br /> °PT April 18, 1974 � <br /> suen_cr 1�22 Aoyt �n�r e� �-,� r.:�r �vrteu� �,.:,v!i::,,ior. <br /> An Glectrical Inspection was �nade at 1722 lioyt as you requested. 'Phe folloo:ing <br /> conditions werc found: <br /> The panel had at one time been protected aith fuse stats as evidence of tlie <br /> mangled bases tltat are left. Puse stats and non-tamperaUle must be used. All <br /> fuses in the panel �aere 30 amper rated on wire that is approved for 15 amp, <br /> Circuits were doubled up on the fuses. This is not permitted by code. �3otl� <br /> panels are in the lower apartme�.tt and violates the code rule oP having the <br /> service uvailable to eacl� te.:!�:t. There were insufficient number of outlets <br /> in tl�e aparLments which caused the use of extention cords. Of the five rooms <br /> in each of the apartmeuts, I found three outlets upstairs and four outlets down <br /> stairs. Tl�e light fi�:ture in the downstairs apartment had been removed because <br /> of tl�e insulation Uurr.ed off the fixture ioire. Tlic two exposed wires have <br /> been added to the orig-,inal housc �oiring and oP what I could see, iC is not <br /> acceptable to code. <br /> The upper apartmenL' is fed off one circuit only. There are no appliance circuits <br /> and also a lack of outlets. As a witole, I do not fcel the house is adaquatcly <br /> wired to be used as a duplex. <br /> Larger size paneis should Ue installed for Uoth apartments in addition to more <br /> outlets in each, <br /> Respecttully <br /> L. J. llouqlierCy <br />