Dry 10'b <br />LVIKI <br />torte 2 2007 <br />DRY PIPE <br />SPRINKLER SYSTEM <br />The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 <br />Telephone: 269.945-9501 Technical Services: 877-384.5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com <br />6 Sprinklers - For types, orifice sizes, and temperature ratings, see the sprinkler section of the Engineering and Design Data <br />book. Sprinklers installed in the pendent position must be of the DRY PENDENT TYPE when the piping and sprinkler are <br />not in a heated area. Sprinklers are spaced to cover a design -required Door area [from 36 to 225 square feet (3,344 mz to <br />20.9025 mz)) or as designated in the appropriate standard. <br />7 Inspector's Test and Drains <br />a A test drain valve must be provided: <br />4" (100 mm) and larger system - 2' (50 mm) drain, <br />2-1/2' (65 mm) to 3.1/2' (90 mm) = 1.114" (32 mm) drain, <br />1" (25 mm) to 2' (50 mm) = 3/4" (20 mm) drain. <br />b. All piping must be pitched toward a drain. A drain n.ist be provided at all low points. A two -valve drum drip may be <br />required. <br />c. An inspector's test is required on each system The inspector's test simulates the Dow of one sprinkler. It is used when <br />testing the system to ensure that the alarm will sound and the water will reach the farthest point of the system in less <br />than one minute. <br />8. Pipe Hangers - Specific type, size, and placement requirements as indicated in the appropriate standard. <br />ITEMI DESCRIPTION <br />ITEM <br />DESCRIPTION <br />ITEM <br />DESCRIPTION --1 <br />I <br />2 <br />FCity Main <br />Pumper Type Fire Hydrant <br />11 <br />12 <br />Test Drain Valve <br />Dry Pipe Valve <br />21 <br />22 <br />Dry Pipe Valve House <br />0S. 6 Y. Valve (Optional) <br />3 <br />4 <br />Underground Fire Main <br />Key Valve and k7ad Box <br />13 <br />14 <br />voter Motor Alarm <br />Cross Main <br />23 <br />24 <br />Check Valve <br />Drun Drip <br />5 <br />6 <br />Post Indicator Voive <br />Test Drain <br />15 <br />16 <br />Air Pressure Maintenance Device <br />Accelerator (Optional) <br />25 <br />26 <br />Drain Vole 6 Plug <br />Upright Sprinkler <br />7 <br />8 <br />Ban Drip <br />Fire Department Conriect.oq <br />17 <br />18 <br />Pressure Switch (Hidden) <br />Alarm Line Strainer (Hidden) <br />27 <br />28 <br />Pendent Sprinkler <br />Inspector's Test Valve <br />9 <br />10 <br />Check Valve <br />voter Motor Alan, Drain <br />19 <br />20 <br />Alarn Test Valve <br />Drain Cup <br />29 <br />Inspector's Test Drain <br />0/� <br />