Laserfiche WebLink
b) Second bedroom — approximately 90 square feet = minimum window of 9 square <br />feet wish an opening area of 5.7 square feet (see egress requirements above). <br />3) In addition to the smoke detectors already provided, additional battery powered <br />smoke detectors are required in each sleeping room per Section 110.9.1.99 <br />Electrical Code <br />• Panel installed in clothes closet is not allo%i ed WAC 296-46-23062 <br />• No working clearance @ panel NEC 110.26. <br />• Ungrounded wiring with grounding type receptacle NEC 210-7. <br />Two wires under lug of breaker — UL listing <br />• 30 amp breaker with t l2 wire —should be 20 amp maximum NEC 240-3. <br />Wire to hood fan damaged <br />Headers on 120V circuit exceeds 50% of branch circuit NLC 210-23. <br />Both living units fed from single panel, each tenant needs access to breakers NEC <br />210-25 and 240-24. <br />• No permits on file for the work performed <br />Plumbing Code <br />• Dishwasher drain requires vent UPC Section 1002.1. <br />There may be additional items that were inaccessible. <br />