Laserfiche WebLink
1 S. All stonn ���atcr facilitics sh.ill bc dcsigned in accordancc with thc standards and/or dcsign policics in <br />cffect at thc time of SEPA application. <br />19. "I'ablc 1-5.7 of ihc City's Storm \'Vatcr Management �4anual contains an error in lhe "d' valucs for <br />shcct Ilow. "I'hc column of valucs should read "0.011, 0.05, 0.15, 0.24, 0.�11, 0.13, 0.40, 0.80". <br />20. Acccss - Thc ]ntcrnational I�irc Code rcquires lhat all ncw structurcs shall provide Fire Department <br />acccss roads to within 150 fcet of all portions of thc ground �oor. Pirc Department access ro�ds (I� irc <br />Lancs) shall providc a minimum of 20 fcct in width of unobstructcd, pavcd driving surface with a <br />minimum cican c�ight of 13'G". InsiJc turn radii must bc 35 fcct. Slopc approach and departurc <br />augles must not excecd 10 degrecs. Firc lane grade must not excecd IS perccnt. Firc Lancs �vill <br />Uc postcd and maintaincd ,�s rcquircd by Ihe Fire Department. <br />The Hardeson Road e►rlry may not meel fire depaihnent 'require�xents. <br />21. V✓hen acccss to or ���ithin a structure or an arca is unduly dil7icult bccausc of sccurcd upcnings or <br />whcre immcdiatc access is neccssary 1'or lifc saving or tiro-fighting purposcs, the I�irc llepartmcnt <br />may reconuncnd or rcquire a key box to bc installed in an accessible location. A rapid cntry system <br />may also bc dcsiroblc in ordcr to avoid unnccessary damagc whilc making cntry to any building <br />during an cmcrgcncy situalion. <br />22. Plcasc call (425) 257-8123 for fiirthcr infiirmation. <br />23. Pirc lanes shall bc providcd as rcquircd in G��crett Municipal Codc 46.44. I�irc lancs shall bc <br />idcntiticd by red curbs �vith whilc stcnciling stating "NO PARKING - FIRG LANG" anJ vcrtical <br />signs stating "NO VARKING - PIRG LANL' -'1'OW AWAY'l_ONG" I_ocation shall bc approved by <br />thc 1'irc Marslial. <br />2d. Securitv Pencc - An}� secw�ity lence crecled around the wnstniction site shall bc located so as to not <br />obstnict m�p cxisting hydrnnt, firc protcction cquipment, or I�ire Department access. If I�ire <br />Department access is obstructcd, gates or atlicr openings shall be pro��ided for access. <br />25. Prcmisc Identification - Yrcmiscs shall Uc cicarly idcntificd by the corrcct address at the strcet cntry. <br />f3uildings shall bc cicarly idcntificd so as to Uc ��isiblc and Icgiblc from thc acccss road. Individual <br />apartmenis and suitcs, wherc applicaUlc, shall be cicarly and Icgibly idcntified from thc access road. <br />2G. PR1:111SF, IDI,N7'IFICA'TION AND ALL REQUIRF.D FIRr DEPARTMENT ACCESS <br />ROADS AND FIRE HYDRAN'1'S SHALL BE IN SERVICE PRIOR TO C0111M1?NCE11tENT <br />OF CONSTRUC'I'ION. <br />27. 1'irc I I�dti rants - Locations as planned are acceptable. <br />2R 13ased upon 7,850 squarc Icct of �I'ypc V-i3, sprinklered construction, the fire tlo��� requirement is <br />1,500 gpm. <br />I2 <br />