Laserfiche WebLink
: � • � <br /> � �� , <br /> 5. 'fhe ventilation for the floor appears to be less than 1 sq. ft. of ventilation for each <br /> I50-sq. ft. of under floc�r azea. Please serify that requirement is met. <br /> 6. Provide smoke detectors in all sleeping rooms and in the corridor or area giving <br /> access to each separate sleeping area. Detectors shall be installed on each story <br /> and in basements. <br /> 7. Provide minimum header size for windows in study. Verify existing headers as <br /> adequate. <br /> Provide a response letter showing where each item in this correction letter is <br /> addressed on the plan set. <br /> Upon resubmital of the drawings, your application will be given priority and plan <br /> review will commence. <br /> All required submittals shall be of sufficient detail ancl contain sufficient infotmation <br /> to ensure that the proposed structure will be constructed in compliance with all <br /> adopted codes. <br /> Sincerely, <br /> Jeff Heilman <br /> Development Technician <br /> 1H:jt:c000S-001 <br />