Laserfiche WebLink
t <br />n <br />7. Provide minimum R-10 insulation at all headers in exterior envelope per Table R402.1.1 <br />WSEC. <br />8. Provide footing size and location for bottom landing at entry stairs. <br />9. Specify stringer size and quantity at exterior stairs. Show how stringers are attached to <br />landings and deck. <br />10. Show how dwelling unit is provided with the additional energy efficiency credits per <br />Section R406.2 WSEC (1.5 required). <br />11. A minimum of 75 percent of permanently installed lamps in lighting fixtures shall be <br />high -efficacy. <br />12. Provide section/detail fo, deck construction at front door where deck extends above the <br />garage below. <br />Please prepare a response letter showing where each item in this correction letter is <br />addressed on the plan set. <br />Upon resubmittal of the drawings, your application will be given priority and plan review will <br />recommence. <br />All required submittals shall be of sufficient detail and contain sufficient information to ensure <br />that the proposed structure will be constructed in compliance with all adopted codes. <br />Sincerely, <br />j. IV � <br />Jeff Heilman <br />Development Technician <br />425-257-8976 <br />Email: jheilman@ci.everett.wa.us <br />