� <br />PllBL�C K/OrrXS <br />��//.l� r� ��y/ <br />I J . <br />.1)''� l f <br />August 22, 1991 <br />Mr. James R. Graves <br />514 Olympic Blvd. <br />Everett, WA. 98203 <br />RE: O�mer: <br />Job Address <br />Plan Check No <br />Dear Mr. Graves: <br />James R. Graves <br />514 Olympic Blvd. <br />91/27368 <br />In response to your application for a construction permit, your plans have <br />been examined and you are advised that the issuance of a pezmit is being <br />withheld for the reasons listed below. <br />1 <br />2 <br />4X8 beam at center, supporting roof, is overstressed in bending ana <br />in shear. Provide new beam size, specias and grada. <br />Floor plan does not shov locations of openings in exterior and/or <br />interior walls. <br />3. The 1/2" plywood sheathing indicated in 3 corners is required to be <br />a ninimum of 4'X8' to meet lateral bracing requirements. On at <br />leas� 3 sides, there are either vir.dows or doors chat ara less than <br />4 feet from the corner. Provide minimum lateral restraint panal(s) <br />per enclosad detail. <br />4. Overflow drains shall be connected to drain lines independent from <br />the roof drains. <br />5. Enclosed rafter spaces formed where ceilings are applied direct to <br />the underside of roof rafters shall have cross ventilation for each <br />separate space by ventilating openings protected against the <br />entrance of rain and snow. The net free ventilating area shall be <br />not less than 1/150 of the area of the space vantilated. <br />CITY OF EVERETT • 3200 Cedar Street • Everett, WA 98201 •(206) 259-8800 • Fax (206) 259-8882 '� <br />