Providence Everett Medical Center <br /> Chapter 246-320 WAC Hospitals <br /> B['ea.st Centec(Outpatieny <br /> Plae Review Comments <br /> c � <br /> g o 8 <br /> � � � <br /> � � � Z <br /> S l � Provide a sink in the film developing area. WAC 246-320-785(1)(b)(v) <br /> Approved 3/18/02 as per eesponse letter dated 3/4l'02 indicating room is only <br /> used for loading of fllm cassettes. <br /> S 2 � What are the boxes in doors 148B and 137B? WAC 246-320-505(2) <br /> Approved 3/19/02 as per response letter indicating boxes are relites in the <br /> doors to the soiled utility and housekeeping. <br /> S 3 � Obtain approvals for Radiation Shielding from DOH-Radiation Protection for the <br /> Stereotactic room 132B. Contact Alton Jenkins at(360) 236-3231. Provide a <br /> copy of the approval letter. <br /> Approved 3/18/02 as per respon.se letter dated 3/41U2 and inform�tion memo <br /> indicoting shielding review for a rtwmmo stereotactic biopsy system is not <br /> required. <br /> S 4 � Locate housekeeping for this area. WAC 246-320-785(1)(a)(iii) <br /> Approved 3/19/02 as per response letter locatlng housekeeping on same fbor <br /> across[rom waiting lobby. <br /> S 5 � Provide manufacturers labeled carpet specifications and radiant panel test report. <br /> WAC 246-320-525(6)(b) <br /> Approved 3/19/02 as per response letter and manufacturers speci0catk;na <br /> stating"I.ees, Kerry D4736,Broadloom". <br /> S 6 � Place a reduced pressure backflow assembly on the water supply to film <br /> developers. WAC 246-320-525(4)(a) <br /> Approved 3/19/02 as per response letter locating reduced pressure backtbw <br /> assembly on the revised plumbing plwn P2.0 and indicated in key notes N2. <br /> Page 3 of 7 Plan Review Comments for Project 116433 <br /> Review Key: A=Archiiccl F=Fire&Lifc Sa(ety S=Sanitanan M=Mahanical/L''earical C=Conference Nole <br /> 77 <br />