e . B <br /> � e > <br /> � � € � <br /> f <br /> oLc u < � <br /> S 7 � Spetify sinks and fittings. WAC 246-320.525(4xc) <br /> Approved 3/191�02 as per tespoAse ktter and athchi�pinmbf�ubednk. <br /> S 8 � Equipment layout plan A8.1 calls-out for the film processor to bc plumbod and <br /> vented. Plumbing plans do not refloct this requirement. Pkase coadinate. <br /> Approved 3/19I�02�s per essponse ktter�nd�evbed pl�n e6afs P1.0 and <br /> P2.0 showin6 the vent�u��d Plumbin�d the fYn►proceMa'. <br /> S 9 � If exam rooms are used for more than non-im•35ive breast exams and education, <br /> they shall �ot be carpeted. Pleace revise your fun.:tional program. WAC 246- <br /> 320-525(6xb) <br /> Approved 3/19r02 aa per�espons� . a•' P Mnctioml Prosnm <br /> indkadng rooms IOSB and 121H, o�• :fsed tor non-invasive <br /> breast exams�nd patknt educatrio <br /> S 10 � Plans E2.0 and A 1.1 do not agrce on th: v �. kooms IOSB and 1218. Is this an <br /> exam room or a procedurc room? Pi-ase:wnress in functional progratn. <br /> WAC246-320-505(2) WAC246-320-SIS�(Sxd) <br /> Approved 3/19IO2�a per reeponx ktter Md�evfefon d pl�n sheet E2.0 <br /> I�belin6�s exam�ooms as�vdl �a tevirAn6 tYe hncHoml pro�r�m. <br /> S 11 � Provide medical emergency signal devices in exh mammography room. <br /> sterotactic,and procedure rooms. WAC 246-320-405(9xe)(i) <br /> Approved 3/19/Ot as per response ktter and revision to p4n sheM E2A. <br /> M 12 [R] Provide fire/smoke dampers for all penetrations of ratcd ccxridors,occupancy <br /> separations or suite enclosures Unifortn Building Code 713.10, 713.11, <br /> 10(W3.43.2.3 &WAC 246-320-99902(9).This includes the existing ductworlc <br /> penetrations of the four small ducts serving[he public lobby. <br /> Approved 03/I1/02 based on responAe received 03105102. <br /> M 13 � Provide tampeiproof receptacles for ground-fault circuit intertupters in <br /> Exam/Prceedure rooms in accordance with WAC 246-320-405(9)(e)(ii) and <br /> Table 525-5 of WAC 246-320. <br /> Approved 03/11/02 based on drawings tticeived 03I051�02. <br /> Page 4 of 7 Plan Review Comments for Projact N 6433 <br /> Review Kcy: A=Architec� F=Fire&Life Safery S=Sanitarian M=Mech�iul/Electrical C�Cemfe�ence No1e <br /> V� <br />