Laserfiche WebLink
e . $ , <br /> � e � <br /> � � <br /> t <br /> � 3 < � <br /> S ? � Specify sinks and fittings. WAC 246-320-525(4)(c) <br /> Approved 3/19/�02 as per response ktter aed�ttsching plumbios sc6eduk. <br /> S S � Equipment layout plan A8.1 calls-out for the film processor to be plumbed and <br /> vented. Plumbing plans do not reFlect this requirement. Please coordinate. <br /> Approved 3/19/02 as per respoese ktter and revised plan sheefs P1.0 and P2.0 <br /> showing the ventlng and plumbing of the film procegsor. <br /> S 9 � If exam rooms are used for more than non-invasive breast exams and education, <br /> they shall not be carpeted. Please revise your functional program. WAC 246-320. <br /> 525(6)(b) <br /> Approved 3/19/02 as per response letter and revised funcUonal program <br /> indicating rooms lOSB and 121B arc Exam Rooms used for non-invasive <br /> bresst exams and patient education. <br /> S 10 � Plans E2.0 and A1.1 do not agree on the use of Rooms lOSB and 121B. Is this an <br /> exam room or a pmcedure room? Please address in functional program. <br /> WAC 246-32U-505(2) WAC 246-320-815(5)(d) <br /> Approved 3/19/02 as per response letter and revision o[plan sheet E2.0 <br /> labeling as exam rooms as well as revising the functionnl prognm. <br /> S I 1 � Provide medical emergency signal devices in aach mammography room, <br /> sterotactic, and procedure rooms. WAC 246-32Q-305(9)(e)(i) <br /> Approved 3/19/02 as per response letter and revision to plon sheet E2.0. <br /> M 12 CL�I Provide fire/smoke dampers for all penetrations of rated cocridors,occupancy <br /> separations or suite enclosures Uniform Building Code 713.10,713.11, <br /> 1004.3.4.3.2.3 & WAC 246-320-99902(9). This includes tlie existing ductwork <br /> penetrations of the four small ducts serving the public lobby. <br /> Approved 03/11/02 brsed on response received 03/OS/02. <br /> M 13 � Provide tamperproof receptacles!'or ground-fault circuit intertupters in <br /> Exam/Procedure rooms in accordance with WAC 246-320-405(9)(e)(ii)and Table <br /> 525-5 of WAC 246-320. <br /> Approved 03/11/02 based on drawings received 03/OS/02. <br /> Page 4 of 7 Plan Review Cotnments for Project N 6433 <br /> Revicw Kcy: A=Architect F=Firc&Life Sa(cry S=Smitari�n M=Mechanical/Electriul C�ConFamce Nde <br /> �i� <br />