�� ! 1 <br /> Mr. Tim Tyler <br /> Pape 2 <br /> September 22, 7992 <br /> Our second meeting on September 17, 1992, was scheduled to review the city of Everett's <br /> interpretation of these UBC sections. The application of these sections produced the folfowinp <br /> determfiation: <br /> 1. Fire dampers are not required in corridor separation walls if the steel duct has no openinps <br /> into the corridor and is a minimum 26-paupe. <br /> 2. Fire dampers are required when passinp throuph occupancy separations includinp rooms <br /> defined as a one-hour separation in Table 10-A. <br /> 3. Fire dampers are not required at the base of the two-hour-rated shafts if the shaft is of <br /> noncombustible construction extendinp to the underside ot a three-hour-floor/ceilinp <br /> separation and fire dampers are insialled when the duct dxits the two-hour shaft. <br /> The attached copies of the architectural drawinp, Sheet A-16, and the mechanical drawinps, Sheets <br /> M4.1, M4.2, and M4.3, have been revised to reflect the cumulative determinations from both <br /> meetinps which could reduce construction costs. <br /> Sheet A-16 has been provided to indicate, in color, the revised wall ratinps of the main floor <br /> F.merpency Oepartment suite 19,34P square feetl. <br /> As we diacussed, Rooms M023, M025, M052, and M056 are less than 100 aquare feet and do not <br /> require a one•hour-occupancy separation as stated in Table 70-A of the UBC. <br /> The first floor surpery department exceeds 10,000 square feet and cannot be considered a suite. We <br /> have withdrawn our reGuest to consider a portion of this Qepartment a suite because isalatinp this <br /> area with the required occupancy separation will nepate any potential coat savinps. <br /> Sheet M4.1 has been provided to indicate the deletion of fire dampers at the base of the two-hour <br /> shafts. <br /> Sheets M4.2 and Md.3 have been provideJ to indicate the deletion of fire dampers resultinp from <br /> acceptance of the suite cencept on the main �ioor, as well as the corridor damper exception on the <br /> main and first floors. <br /> I am confident you will find all revisions noted in the attached drawinps consistent with our mutual <br /> underatandinp at the two meetinps. I have provided two copies of each drawinp for your review. <br /> Please return one approved copy to have available on site Aurinp inapection. <br /> We appreciate your prompt attention in assistinp Providence Hospital ta reduce unnecessary <br /> construction costs. Please contact me if you have any questions or concerns. <br /> Sincerely, <br /> 80 SH & NALL ARCHITECTS, P.S. <br /> oore, AIA <br /> dmo <br /> cc: Scott Bond, Providence Hospital <br /> Jim Lorenzen, Providence Hospital <br /> � <br /> i. <br /> i <br /> i <br />