My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
10124 MERIDIAN AVE 2016-01-01 MF Import
>
Address Records
>
MERIDIAN AVE
>
10124
>
10124 MERIDIAN AVE 2016-01-01 MF Import
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
2/25/2017 7:46:05 PM
Creation date
2/25/2017 7:45:53 PM
Metadata
Fields
Template:
Address Document
Street Name
MERIDIAN AVE
Street Number
10124
Imported From Microfiche
Yes
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
82
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
. • � � ' <br /> J 9. The under-floor space between the bottom of the floor joists and �he earth under any building <br /> (except space occupied by a basement) shall have ventilation openings through foucidation <br /> walls or exterior walls. The minimum net area of ventilation openings shall not be less than 1 <br /> square foot (0.0929 m2) for each 150 square feet (14 m2) of under-floor space area. One such <br /> ventilating opening shali be within 3 feet (914 mm) of each corner of the building. <br /> J10. Specify size and location of whole house fan. Show on the plans. <br /> � 11. 1'he Simpson STC is a Roof Truss Clip and not intended to provide a rigid connection of a <br /> post to footing connection. Provide an alternate wnnector capable of resisting uplift and <br /> lateral displacement. <br /> v 12. The plans call out (4) 16d nails for the "Gusset" connection. The connection should be <br /> minimum (8) 16d nails on each side. <br /> Please prepare a respoase letter showing where each item in this correction letter is addres.ud on the plan <br /> set. <br /> Upon resubmittal of the drawings, your application will be given prioriry and plan review will mcommence. <br /> All required submittals shall be of sufficient detail and contain sufficient information to ensure that the pmposed <br /> st�ucture will be constructed in compliance with all adopted codes. <br /> Sincerely, J� „��� � <br /> Jeff Heil <br /> rt�,/ . <br /> Development Technician <br /> S'IMFSc►J �ir �—SID�S <br /> KmIIiWlleilnWB011WJ11R(1013d MeeWiui A�<I <br />
The URL can be used to link to this page
Your browser does not support the video tag.