My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
1922 W MARINE VIEW DR 2016-01-01 MF Import
>
Address Records
>
W MARINE VIEW DR
>
1922
>
1922 W MARINE VIEW DR 2016-01-01 MF Import
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
4/13/2017 9:53:30 PM
Creation date
2/27/2017 6:29:30 AM
Metadata
Fields
Template:
Address Document
Street Name
W MARINE VIEW DR
Street Number
1922
Imported From Microfiche
Yes
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
177
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
/ <br />i y z Z�.--,��� v-�-�-� ,c�_t . <br />3.1.3 Control power trans�ormer was inspected to assure ade- <br />quate capacity for system. <br />3.1.4 Monitor panels were manua.11y operated f.or: <br />o Trip Test <br />o No Trip Test <br />o Non-automatic Reset <br />3.1.5 Zero sequence systems were inspected for symmetrical a]ig- <br />ment of core balance transformers about all current car- <br />rina conductors. <br />3.1.6 Ground fault device circuit nameplate identification was <br />verif.ied for correctness. <br />3.2 Electrical Test <br />3.1.1 System neutral insulation resistance was measured to <br />insure no shunt ground paths exist; neutral-ground discon- <br />nect link was removed, neutral insulation resistance mea- <br />sured and link replaced. <br />3.1.2 The relay pickup current was determined by primary injec- <br />tion at the sensor and the circuit interrupting device <br />operated. <br />3.1.3 The relay timing was tested by injecting 1508 and 3008 of <br />pickup current into sensor. Total trip time was electri- <br />cally monitored. <br />3.1.4 System operation was tested at 558 rated voltage. <br />4.0 RESOLTS <br />4.1 The main bonding jumper on panel #1 has been incorrectly <br />sized. This should be 250 MCM per UL Standard 891, Table <br />23.1. ��„� i-,�. <br />" ,/ <br />4,2 The system on panel #2 was found operat-ional and acceptable. <br />4.3 Ground electrode conductors for. both systems, do not appear <br />to be a 3/0. UL 891 table 23.1 specifies that a 3/0 ground <br />electrode conductor be installed. �. ; �;,- ,� % <br />. -•� � � �� ' � � � '�� <br />
The URL can be used to link to this page
Your browser does not support the video tag.