Laserfiche WebLink
P a q e I 2 <br />CW )102-002 (ifi05 West Wrine Vkw Or) <br />Marth 8, I011 <br />8. Provide safety glass at all windows located within a 24" arc of either edge of a <br />door in the closed position; show on plans. <br />9. Open risers are permitted, provided that the opening between treads does not <br />permit the passage cf a 4 inch diameter sphere. <br />10. Specify U-value of all doors and windows installed or modified for this project. <br />li. Rigid insulatton is typically R-5 per inch. A 3�/z" framing cavity would provide a <br />total of R-17.5. Washington SWte Energy Code (WSEC) requires R-21 in exterior <br />walls. Please provide clarification of rigid insulation proposed. <br />12. Floor insulation is required to be R-30 insulatlon installed without compressfon <br />and supported at not more than 24" o.c.. Please clarify installation and type of <br />insulation at floor joisks, <br />Please prepare a response letter showing w6ere each item in this correction letter is <br />addressed on the plan set <br />Upon resubmittal of the drawings, your application will be given prioriry and plan rpview will <br />recommence. <br />All required submittals shall be of sufficient detail and contain sufficient information to ensure <br />that the proposed structure will be constructed in compliance with all adopted codes. <br />Sincerely, <br />�� <br />]eff He Iman <br />Development Technician <br />425-257-8976 <br />Email: iheilmanC�ci.everett.wa.us <br />s/kcdusaV��maNcwi�o]�o01(. �o: west wahne v�e�. or) <br />7Z <br />