18) The method of providing fresh air to the dwelling units should be detailed on the plans. Section <br /> 302.3.5.2 <br /> Windows in units will be ventilated windows selected by the architect that will comply <br /> with 2006 Washington State VIAQ. See M6.0 and M6.1. <br /> 19) The mechanical plans show the kitchen exhaust fans 'by architect'. The fans should be <br /> shown on the plans as a minimum of 100 cfm. Table 3-1 VIAQ. <br /> The kitchen exhaust hoods are being selected by the architect, a note was added to the <br /> plans for a minimum airflow of 100 cfm for all kitchen hoods. The kitchen hoods will be <br /> submitted for approval by RICE Group, Inc. See M6.0 and M6.1 <br /> 20) The whole house fans for the dwelling units over 1001 square feet should be shown at a <br /> minimum of 60 cfm. Table 3-2 VIAQ. <br /> The whole house fans selected for units over 1001 square feet have been reselected at 60 <br /> cfm. See M1.1. <br /> Jeff, please let me know if you have any questions regarding these responses to the comments <br /> from the permit review. <br /> Sincerely, <br /> Paolo Mauro <br /> RICE Group, Inc. <br />