Laserfiche WebLink
4. Ramp landmqs at a change of direction are required to be 60 inches square, per ICC <br />A117.1 secUon 405.7A, to accommodate a ciear turning space per ICC A117.1 sedion <br />304.3. <br />5. The drawings should indicate a sigr to mark the accessible building entrance, per IBC <br />section 1110. i, since nut all building entrances are accessible. <br />6. A section through the door entry on the accessible route should be shown on ihe drawings. <br />The in[erior and exterior door landings are required to be no more than Y< vertical belew <br />the threshold of the door, per ICC A117.1 section 303.�, Yz inch if beveled. <br />7. The hardware set for the accessible entry door should be identified on the drawings: <br />. The door dearance required at the accessible entry is 12 inch minimum clear, if <br />both a doser and a latch are provided, for a depth of 48 inches, per ICC A117.1 <br />fgure 404.2.3.1 (b). To exit from this same door, a clearance of 18 inches <br />minimum for a depth of S feet is required per Alll.l figure 404.2.s.1 (a). <br />• — - -� - � �, w,,, . _��, �, , �.,��� �,,. �,��. ,. <br />� ��, � <br />� — <br />. J.�-_ �, ,�.� <br />I'� ._ , <br />� <br />-i�i'I - - - - - ��� <br />ta)nc�.�nca�o..:n r,;vu�n� <br />� � � <br />� � , <br />_ I <br />a�� _ _ -- -,in{-� <br />� � <br />�m �,o��i tpomaca <br />a�.•,n S�Ue <br />1. 1he door at the accessible entry is required to have door hardware that does not <br />require tight gresping, tight pinching, or tv✓isting, per IBC section 1008.1.9.1. <br />II. Handrails should be shown on the drawings on both sides of all exterior stainvay riscrs and <br />the new ra���p, per IBC sections 1009.12 and 1010.8 <br />• Handrail hcight, profile, and:extensions should be shown on the drawings for both <br />the stairs and the ramp, per IBC section 1012. <br />9. Guards are required where the eleva[ion change on the sidc of the walkway, ramp, stair, <br />land�ng or paved area exceeds 30 inches to the floor or grade below, per IE3C section 1013. <br />• Guards are required to be 42 inches high minimum, per IE3C section 1013.2. <br />• The opening limitation within a guard �s less than 4 inches, except from 36 inches <br />to 42 inches, where the opening limitation is /ess fhan 4 3/8 inches, per IBC <br />sec[ion 1013.3, exception (1), or at lhe triangular openmg al the open sides of a <br />stair where the opening limitation is /ess than 6 inches, per IBC section 1013.3, <br />exception (2). <br />10. Riscr and tread dimensions on the existing exterior stairs should be shown on the drawings <br />to determine if they meet the minimum requirements for dimensional uniformity, per 16C <br />section 1009.4.4. For new commercial buildings, the stair maximum riser height is 7 inches <br />and minimum tread depth is 11 inches, per IBC section 1009.4.2. <br />7hese comments address building issues only. Revisions or additions may be required by othcr <br />�epartments (U[ilities, Public Works, or Planning). Upon resubmission of the drawings, plan review <br />will resume and your application will be given priority. All re�uired submittals must be of suffcient <br />�� <br />