Laserfiche WebLink
Fire Supvression (Sprinkler S stem - An approved automatic suppression system shall be <br />provided as required by Ciry Ordinance No. 1902-92, Chapter 16.76, of the Everett Municipal <br />Code. <br />Plans for any such system shall be submitted to the Building Department and the Everett Fire <br />Department for examination and approval. Such plans shall mclude plans for the underground <br />mains that will supply the sprinkler system. <br />Aboveground sprinkler piping shall be:�ydrostatically tested as esiablished in NFPA Standard <br />13. Underground piping shall be hydrostatically tested and flushed as established in NFPA <br />Standard 24 for private fire mains. All such tests shall be witnessed by a Fire Department <br />inspector. Call 259-8710 to make an appoinunent for inspection. <br />Contractors' materia:s and test certificates shall be submitted to the Everett Fire Department <br />prior to issuance of any Certificates of Occupancy. <br />Ca11259-8720 for more information. <br />Fire Safetv - Fire safety practices during construction shall be in compliance with Article 87 of <br />the Uniform Fire Code. <br />10. Trash Collection - Dumpsters over 1.5 cubic yards capacity shall be located a minimum of 5 <br />feet from tbe building [UFC 11.302(b), 1991 Edition]. <br />WMB:Iw <br />cc: Gordon Witcher, Public Works <br />Dan Mathias, Public Works <br />� <br />