Laserfiche WebLink
LeGault Nursing Home <br /> HFCU 074421-1092-1 <br /> October 7, 1974 <br /> PaBe z � <br /> REVIEW OF TEiF. STATF. FIRE MARSAAL <br /> 1. Show width of all doors, rooms to corridors; also, doors to outside. <br /> 2. All doors, rooms to corridors, shall be approved 1-3/4 solid core. <br /> 3. Second floor plan and basement plan not ehown. This is required. <br /> 4. Show required separation between first fluor and second floor. Also <br /> between firet floor and basement. <br /> 5. Show all areas now equipped with approved eprinklera. Also, new <br /> areas. <br /> 6. Show locations of all smoke detection devices and heat sensors. <br /> 7. New vindowa adjacent to outside stair shall be 1/4" wire glass set in <br /> steel frames. <br /> 8. St�ow locations of all fire alarm warning devices and pull box locations. <br /> 9, An approved second means of egress is required at the ground floor. <br /> 10. Ceiling tile and assembly will be reqvired te be one-hour approve3 <br /> assembly. <br /> Further study of more detailed plans will be required. <br /> All review items under Part A and i[ems of the State Fire Marshal should be <br /> individually answered using our numbering system. These answers should <br /> acccipaay rc�ub�ission of plans. <br /> Sincerely, <br /> � <br /> ��i � , <br /> � . <br /> ������'t` l' •�' ' � � <br /> F. M. Noecker, Supervisor <br /> Construction Unit MS 3-1 <br /> � Office of P.lanning and <br /> Health Facilities <br /> FMN:GP:se � <br /> cc: State Fire Marshal <br /> Local Building Departmeni <br /> A. L. Scheine, Architect <br />