Laserfiche WebLink
32.Detaiis should be submitted for lateral bracing wilh compression struts for the <br /> suspended ceiling. UBC Standard 25-2, Table 25-A, FooMote 1. <br /> Comment noted. Please refer to revised drawings indicating requirements per <br /> general conshuction reference notes. (33 thraugh 36) <br /> 33. It should be shown on the plans that a listed smoke detector be placed near the <br /> elevator entrances that upon activation will prohibit the elevator from opening and <br /> retum it to the main floor. See other requirements per Secdon 30032 <br /> 34. Elevator hoislways should be vented per the �equirements of Sectlon 3004. <br /> 35. Elevator machinery rooms should be vented per the requirements of Section 3005 � <br /> 36. Elevators are regulated by the Washington State DepaRment of Labor and I <br /> Industries. It is suggested that they be contacted for additlonal requirements. <br /> ExltMg <br /> I. The occupant load of the roof garden is currendy calculated at 57 occupants based <br /> on an occupant load factor of 15 per Table 10-A. The size should be reduced so that <br /> the occupant load is less than 50. Section 1001.6 <br /> Size and location of roof garden has been modified in order to meet these <br /> requirements. <br /> 2. Per comments raised previously, all units open into corridors (except unit A). The <br /> entry doors should be shawn to be 20 minute assemblies. <br /> Comment noted. Please refer to revised drawings showing new door and <br /> hardware schedule. <br /> 3. It should be noted on the plans that all twenty-minute doors in the corridors should <br /> also have smoke and draft control gaskets. Sectlon 1005.8.1 <br /> Comment noted. Please refer to revised drawings showing new door and <br /> hardware schedule. <br /> 4. Emergency exit lighting should be provided in rooms (except dwelling units), stairs <br /> and corridors. An emergency power supply for exit illumination should also be <br /> provided. Section 10122 <br /> Comment noted. Please refer to revised drawings indicadng requirements per <br /> Elecfical Design Build perfortnance specification reference notes. (4 through 6) <br /> � �� �� � - ��.n� � �.i5� <br /> �ililll'.`I ':I'��\�Tkl':I',T ii�..i � i� ii�;i�a,.���i�,� <br /> II��fRf�111�1�f;i�1��i�Rfi��l61'�RI�IICDEiIGI'II;T����;p�161�:1RCHITE�TORE !IIU�RI��I1�G1111E�ORD�IG1!fRI�IICDG�IGII��1�,I�D�GI <br />